Loading chat...

DE HB376

Bill

Status

Introduced

4/22/2010

Primary Sponsor

Edward Bennett

Click for details

Origin

House of Representatives

145th General Assembly

AI Summary

  • Requires the State Fire Prevention Commission to promulgate regulations for floor proximity emergency lighting in all new buildings, occupancy conversions, mixed occupancy buildings, and additions/repairs to existing buildings.

  • Emergency lighting fixtures must activate automatically within 5 seconds of power loss or fire alarm activation, provide illumination for at least 90 minutes, be fully-recessed within 36 inches of the floor, and be UL924 listed and ADA compliant.

  • Mandates floor proximity exit signs located 6-18 inches from the finished floor at all exit access and exit doors, in addition to existing exit sign requirements.

  • Exit signs must illuminate automatically within 5 seconds of power loss or alarm activation and be either UL924 listed (internally illuminated) or UL1994/ASTM E 2072 compliant (photoluminescent), with minimum 60 minutes of illumination for internally illuminated signs.

  • For exit doors, signs must be mounted on or adjacent to the door with the nearest edge within 4 inches of the door frame.

Legislative Description

An Act To Amend Title 16 Of The Delaware Code Relating To Fire Prevention.

Last Action

Introduced and Assigned to Public Safety & Homeland Security Committee in House

4/22/2010

Committee Referrals

Public Safety & Homeland Security4/22/2010

Full Bill Text

No bill text available