Establishes Chapter 66D requiring all buildings (except 1-2 family residential units) to implement testing and inspection programs for HVAC Fire Life Safety Dampers and Smoke Control Systems to prevent fire and smoke spread.
-
Mandates Fire Dampers, Smoke Dampers, and Combination Fire/Smoke Dampers be inspected and tested once after first year of installation, then every 4 years thereafter (every 6 years for hospitals), using visual inspection methods per NFPA 80 and NFPA 105 standards.
-
Requires Smoke Control Systems be tested semiannually (dedicated systems) or annually (non-dedicated systems) to verify airflow quantities and pressure differences are code compliant across smoke barriers, air makeup supplies, and exhaust equipment.
-
Establishes qualifications for inspectors, including state/local fire department personnel or technicians certified as HVAC Fire Life Safety Technicians under ISO/IEC 17024 standards and employed by contractors with workers' compensation insurance.
-
Imposes $100 daily civil penalties for non-compliance, requires building owners to submit Certificates of Operation to Municipal or State Fire Marshal within 30 days, and mandates public posting of inspection verification in building lobbies; deficiencies must be corrected within 30 days.
Legislative Description
An Act To Amend Title 16 Of The Delaware Code Relating To Fire-resistance-related Construction.