All licensed adult residential care providers in Louisiana must have a permanently installed generator or Louisiana Department of Health-approved alternative electrical power source with sufficient onsite fuel for 72 hours of full-load operation
-
Generators must simultaneously power life safety systems, patient care lighting, medical equipment, potable water and sewer systems, medication dispensing and refrigeration, dietary services, laundry, and HVAC (50% capacity for facilities built before August 1, 2026; 90% for newer facilities)
-
Facilities must maintain fuel delivery agreements to extend generator operation to 168 total hours during a single emergency event
-
Waivers available for pre-August 2026 facilities lacking physical space or facing governmental ordinances preventing compliance, but waived facilities must submit annual emergency plans to parish offices of emergency preparedness
-
Compliance deadline is December 1, 2027, with the Louisiana Department of Health authorized to grant one-time extensions up to 12 months; the State Fire Marshal determines compliance and reports violations to the department